Products Description
I. Product Positioning
Island Protection / Grid Disconnection Relay Protection Device, compatible with gas turbines, diesel generator sets, waste heat power stations, distributed photovoltaic / biogas generators. When the generator sets are connected to the grid, it monitors grid abnormalities. In the event of grid voltage loss / frequency loss / phase offset, it instantly trips the grid connection switch of the generator set to prevent the island from asynchronous grid connection and damage to the generator set. This is a standard component of the European VDEW / German grid standard and is often used in conjunction with Woodward 505, 8440-1706D speed control boards.
Integrated Protection Functions (ANSI Standard Protection Codes) Table
Protection Type ANSI Code Explanation
Over/Under Voltage Protection 59/27 Three-stage voltage time curve, customizable inverse-time U-t characteristic
Over/Under Frequency Protection 81O/81U 3 levels of frequency setting + delay setting
Vector Surge (Phase Angle Offset) 78 Vector Surge MRN3-1 core, rapid tripping for grid disconnection phase change (millisecond level)
Frequency Rate of Change ROCOF (df/dt) 81df Optionally available, rapid decoupling for frequency drop
Three. Electrical Specification Parameters
Voltage Input: PT secondary 100V (MRN3-11D standard); optional 230V/400V three-phase voltage sampling, power consumption < 1VA
Applicable Frequency: 40~70Hz (50/60Hz units are universal)
Power Supply: AC/DC 85~265V universal auxiliary power supply
Output Contacts: Multiple passive trip dry contacts (5A/250VAC), one alarm, one grid trip
Communication: RS485 Modbus-RTU, equipped with SmartView software for parameter setting and fault recording reading
Installation: Standard DIN rail / 19-inch plug-in frame installation, plug-and-unplug with core-pulling structure
Operating Temperature: -20℃~+60℃, industrial protection inside cabinet
Four. MRN3 Model Classification
MRN3-11D (This product): Vector offset + over/under voltage + over/under frequency (Vector Surge as the main criterion, mainstream for European and American thermal power / diesel units)
MRN3-21D: ROCOF (df/dt frequency rate of change) as the main criterion, used for wind power and photovoltaic distributed power sources
MRN3-31D: Full function (vector + ROCOF + voltage/frequency) high-end model
Five. Compatible with Woodward Speed Control System
Companion: 505 speed controller, 8440-1706D, 8290-191, 8402-271 generator speed control module, forming a complete set of unit speed control + grid decoupling protection system, commonly used spare parts for power plants, refinery turbine units.
You May Need
| WOODWARD | 9907-029 |
| WOODWARD | LS-5 8440-1946 |
| WOODWARD | 5460-667 |
| WOODWARD | 9906-619 |
| WOODWARD | 9907-173 |
| WOODWARD | 5466-258 |
| WOODWARD | 5466-316 |
| WOODWARD | 5437-843 |
| WOODWARD | 5501-467 |
| WOODWARD | 9905-969 |
| WOODWARD | 9905-971 |
| WOODWARD | 5501-376 |
| WOODWARD | 9905-968 |
| WOODWARD | 8516-085 |
| WOODWARD | 9905-021 |
| WOODWARD | 8440-1934 |