Woodward 2301E 8273-1011 Digital load distribution

Brand/Manufacturer: Woodward

Order Number: 8273-1011

Country of Origin: USA

Condition: Original Brand

Lead Time: Available in stock

Payment Term: 100% TT In Advance


Send Inquiry
Power Duke Automation Equipment Co., Ltd.
Sales Manager: Anne
WeChat: +86 19336875129
Email: Anne@yuanmiaoautomation.com
We can offer you the best price!
Image 2
Image 2

Products Description

WOODWARD 2301E 8273-1011 | Digital Load Distribution / Load Sharing Governor (Combined Unit Load Distribution Speed Controller) 


Terminal surface

I. Product positioning

8273-1011 = 24VDC ordinary industrial type 2301E, Woodward classic generator set multi-machine parallel load distribution + speed closed-loop integrated controller, upgraded to replace the old model 2301D/2301A, compatible with diesel/gasoline generator sets and power stations, self-owned power plants, and auxiliary power stations of ships, achieving automatic parallel distribution of active loads and stable frequency speed regulation for multiple generator sets.

Model distinction: 8273-1012 is intrinsically safe explosion-proof Zone2 model (chemical hazardous area), 8273-1011 is conventional industrial 24V power supply.


Electrical specification parameters Table

Project Parameters

Power supply DC 18~36VDC (nominal 24VDC), total machine power consumption < 15W

Speed measurement input MPU magnetic sensor probe: 0.5Hz~10kHz, adaptive gear tooth count, 0~6000rpm full-scale range compatibility

Power sampling Three-phase CT current + PT voltage, collecting generator active power for load distribution

Actuator output 0~200mA / 4~20mA, direct drive Woodward full series electric actuators (8250 series)

Analog I/O 1 channel 4-20mA setpoint input, 1 channel 4-20mA output

Switching quantity 8 channels DI passive contact input, 4 channels relay DO (5A/250VAC alarm / grid connection control)

Communication RS232 (local debugging) + RS422 (Modbus-RTU, network monitoring) dual serial ports, PC uses Control Assistant software to set parameters

Environmental temperature -40℃~+70℃, metal casing, DIN rail / panel embedded installation, IP20 protection

Size / Weight Approximately 250×125×55mm, net weight ≈ 0.15kg


Three core operation modes (Load Distribution)

Isochronous synchronous parallel operation (mainstream parallel operation)

Multi-generator parallel bus constant frequency operation, automatic precise distribution of active load between generators, soft loading / soft unloading, automatic distribution of load fluctuations, standard mode for backup power station, parallel load lines can achieve equal distribution.

Droop droop mode

Single machine isolated grid / grid external power use, load increase linearly drops speed, multi-generator droop parallel natural equal distribution, compatible with grid connection base load operation.

Base Load base power fixed output mode

After grid connection of the generator, lock fixed active output, 4-20mA remote signal modifies power setting, commonly used in refineries, cogeneration plants.


Built-in engine protection and fuel limit functions

Idle / rated dual speed, start-stop acceleration and deceleration slope anti-skid;

Three-stage torque limit, intake MAP pressure fuel limit oil, start-up oil quantity limit;

Load shedding compensation algorithm: suppress speed rise / drop speed during grid disconnection;

Fault storage recording: overspeed, MPU disconnection, actuator fault historical record query.

V. List of supporting equipment

Speed control actuator: Woodward 8250-1505, 1751 series;

Grid connection protection: MRN3-11D islanding separation relay (grid power loss trip);

Same system speed control: 505 speed regulator, 8280-423 marine speed control board, 8290-191 turbine module.