Products Description
WOODWARD 2301E 8273-1011 | Digital Load Distribution / Load Sharing Governor (Combined Unit Load Distribution Speed Controller)
Terminal surface
I. Product positioning
8273-1011 = 24VDC ordinary industrial type 2301E, Woodward classic generator set multi-machine parallel load distribution + speed closed-loop integrated controller, upgraded to replace the old model 2301D/2301A, compatible with diesel/gasoline generator sets and power stations, self-owned power plants, and auxiliary power stations of ships, achieving automatic parallel distribution of active loads and stable frequency speed regulation for multiple generator sets.
Model distinction: 8273-1012 is intrinsically safe explosion-proof Zone2 model (chemical hazardous area), 8273-1011 is conventional industrial 24V power supply.
Electrical specification parameters Table
Project Parameters
Power supply DC 18~36VDC (nominal 24VDC), total machine power consumption < 15W
Speed measurement input MPU magnetic sensor probe: 0.5Hz~10kHz, adaptive gear tooth count, 0~6000rpm full-scale range compatibility
Power sampling Three-phase CT current + PT voltage, collecting generator active power for load distribution
Actuator output 0~200mA / 4~20mA, direct drive Woodward full series electric actuators (8250 series)
Analog I/O 1 channel 4-20mA setpoint input, 1 channel 4-20mA output
Switching quantity 8 channels DI passive contact input, 4 channels relay DO (5A/250VAC alarm / grid connection control)
Communication RS232 (local debugging) + RS422 (Modbus-RTU, network monitoring) dual serial ports, PC uses Control Assistant software to set parameters
Environmental temperature -40℃~+70℃, metal casing, DIN rail / panel embedded installation, IP20 protection
Size / Weight Approximately 250×125×55mm, net weight ≈ 0.15kg
Three core operation modes (Load Distribution)
Isochronous synchronous parallel operation (mainstream parallel operation)
Multi-generator parallel bus constant frequency operation, automatic precise distribution of active load between generators, soft loading / soft unloading, automatic distribution of load fluctuations, standard mode for backup power station, parallel load lines can achieve equal distribution.
Droop droop mode
Single machine isolated grid / grid external power use, load increase linearly drops speed, multi-generator droop parallel natural equal distribution, compatible with grid connection base load operation.
Base Load base power fixed output mode
After grid connection of the generator, lock fixed active output, 4-20mA remote signal modifies power setting, commonly used in refineries, cogeneration plants.
Built-in engine protection and fuel limit functions
Idle / rated dual speed, start-stop acceleration and deceleration slope anti-skid;
Three-stage torque limit, intake MAP pressure fuel limit oil, start-up oil quantity limit;
Load shedding compensation algorithm: suppress speed rise / drop speed during grid disconnection;
Fault storage recording: overspeed, MPU disconnection, actuator fault historical record query.
V. List of supporting equipment
Speed control actuator: Woodward 8250-1505, 1751 series;
Grid connection protection: MRN3-11D islanding separation relay (grid power loss trip);
Same system speed control: 505 speed regulator, 8280-423 marine speed control board, 8290-191 turbine module.