Woodward 8440-1936 | easYgen‑3000 Series Grid-Connected Controller
8440-1936 Complete Machine
Interface side
Terminal side
I. Product Positioning
Model easYgen‑320, order number 8440‑1936, is a dedicated intelligent controller for Woodward original factory diesel/gasoline generators. It is used for single-machine automation, automatic restart upon mains failure (AMF), generator paralleling, load distribution. It is compatible with diesel generators and biogas generator sets, and is combined with speed control actuators, 505 speed regulators, and 9907‑1200 electro-hydraulic converters for use.
Electrical Power Supply Parameters
Power Supply: DC 8~40VDC (nominal 12/24V battery power supply, diesel generator set standard)
Overall Power Consumption: ≤19W
Measuring Voltage: Three-phase 0~690VAC (50/60Hz universal, 40~85Hz sampling range)
I/O Hardware Configuration
1. Analog Input (AI) (4‑20mA/0‑10V)
3 Programmable Analog Inputs: Water temperature, oil pressure, cylinder temperature transducer collection;
2. Analog Output (AO) (4~20mA): Speed control output, directly connected to Woodward electric actuator/electro-hydraulic converter (connect to your previous 9907‑1200, 8290 series actuators).
2. Switch Input/Output (DI/DO)
DI: 10 Passive Switch Inputs (Stop, Emergency Stop, Oil Pressure Alarm, High Water Temperature, Local/Remote Switching)
DO: 8 Relay Outputs (Starting Motor, Stop Electromagnetic Valve, Alarm, Close/Open Control)
Communication Interfaces (Core)
3 CAN Buses: J1939, CANopen, directly connected to engine ECU (Cummins, Yuchai, Weichai electronic control units, read engine speed, fault codes)
RS232: Computer software debugging, parameter upload/download
Modbus‑RTU (RS485): Connect to DCS/upper computer for remote monitoring of voltage, power, frequency, fault information
Control Functions
AMF Mains Failure Self-Start: Delayed startup of the generator upon grid anomaly, automatic shutdown of the machine when mains power is restored + switch change;
Speed/Frequency Closed Loop: AO output 4‑20mA controls the speed control valve, stable frequency and voltage;
Full Dimensional Generator Protection: Overvoltage/Undervoltage, Overfrequency/Low Frequency, Overcurrent, High Water Temperature, Low Oil Pressure, Over-speed Shutdown Protection;
Event SOE Recording: Start/Stop Records, Fault Storage, Operation Duration Statistics, Maintenance Time Reminder;
Manual/Automatic Non-interfering Switching, local operation through panel buttons.