Products Description
I. Product Overview
The American Woodward 8237 series high-power actuator drive + overspeed protection integrated module. 8237-2597 is the standard drive model, receiving 4-20mA / pulse control signals from the upper-level speed control controller. It directly drives hydraulic / electromagnetic fuel actuators, integrates a three-out-of-two overspeed protection logic, and is installed in a panel-mounted housing. It is suitable for fuel valve driving and safety interlock of gas turbines, steam turbines, and high-power diesel generator sets.
Key Technical Parameters Table
Parameter Item Specification Parameters
Rated Power Supply DC 18~32VDC (nominal 24V, total machine power consumption ≤ 30W)
Drive Output ±24V high-power servo drive, maximum output current 1.8A, compatible with hydraulic actuators
Speed Acquisition 2 MPU magnetic sensor input: 4~20000Hz, input voltage 1~32VAC
Analog Input Channels 2 4-20mA signal input (main control speed command), 1 4-20mA speed conversion output
Switching Circuit 3 independent trip relays (three-out-of-two voting architecture), contacts AC 250V/8A load capacity
Response Speed Full stroke valve position response < 50ms
Communication Bus CAN J1939, Modbus-RTU dual protocol bus
Protection Grade IP65 die-cast aluminum housing, PCB fully three-proof coating against sulfur fog corrosion
Operating Temperature -40℃~+85℃ industrial wide temperature range
Vibration Resistance Index 5g (10~500Hz), shipborne / offshore platform vibration standard
Form and Weight 331×413×136mm, net weight 6.8kg
Safety Certification SIL2, CE, UL, ATEX Zone2 explosion-proof certification
Product Performance
Dual-function integration: combines actuator power drive + unit overspeed protection, can amplify control signal to drive fuel actuator, and independently collect speed to achieve overspeed trip protection, dual circuits do not interfere with each other;
Three-out-of-Two Fault Tolerance Protection: three independent speed sampling, 2/3 voting logic, single-point probe failure does not cause false trip, significantly reduces the probability of false shutdown;
Drive Closed-loop Self-correction: real-time collect actuator valve position feedback, automatically compensate coil temperature drift, oil pressure fluctuation, steady-state valve position control error ≤ ±0.2% FS;
Full Fault Self-check: power reverse connection, output short circuit, probe break, actuator locked rotation, over-temperature real-time alarm and hierarchical output locking, built-in fault record power-off preservation;
Multi-signal Compatibility: supports 4-20mA, 0-10VDC, CAN bus three types of main control instructions access, can be connected to Woodward 5437, 7200 series controllers.
Application Fields
Thermal Power / Gas Turbine Power Station: heavy-duty gas turbine, industrial steam turbine main fuel actuator drive + overspeed protection;
Oil and Gas Extraction Industry: natural gas booster unit, oilfield high-power diesel-driven compressor main control drive;
Offshore Ship Power: ocean-going ships main auxiliary steam turbines, high-power marine generator set safety speed regulation drive;
Self-owned Power Station: steel mills, refineries large-power backup gas / diesel generator system support.
Main Models of the 8237 Series Table
Model Product Positioning Configuration Differences
8237-1247 Economy type low-power drive model One-channel execution output, no three-out-of-two protection, dedicated for medium and small power diesel generators
8237-2597 Standard full-function model (this model) High-power drive + three-out-of-two overspeed protection, main engine standard configuration
8237-3597 Redundant dual-drive model Two independent execution outputs for dual paths, critical units have one-in-use and one-as-backup redundant configuration
8247-1892 8247 cross-series high-end configuration With Ethernet communication, supports remote online configuration and SCADA remote monitoring