Products Description
I. Model Interpretation
IS200TDBTH2A: Base board model
CD = Version suffix (PCB revision batch), the same series also has ABC/ACC/ACD and other sub-versions, the electrical pins are completely universal and can be directly interchanged
Classification: Simplex single-channel non-triple-redundant (TDBTH2 series; TDBTH6 is the TMR triple-redundant model)
Hardware and Electrical Parameters
Power Supply: DC28V system power supply, the maximum power consumption of the single board ≤ 2W, the circuit rated 0.81A
Terminal Configuration: Double-row fence-type terminal blocks, 32 input/output mixed points of switch quantity DI+DO
DI: Passive contact points / 24VDC active input (local valve feedback, local status, interlock contacts)
DO: Relay passive contact output (electromagnetic valve, indicator light, small contactor drive)
Backplane Interface: Central large-sized ribbon connector socket, directly connected to the upper IS220PDIOH1A IO Pack card, back-insertable installation in the cabinet
Environment: Working temperature -30℃ to +65℃, cabinet DIN rail / rack fixed installation
Size: Standard Mark VIe I/O terminal board specification: approximately 215×110×30mm
Core Functions
Field Hardwired Interconnection: Field switch quantity signal lines are connected to the terminal of this board, the ribbon is transferred to the PDIO main control card, isolating field interference and facilitating line inspection and maintenance within the cabinet
Loop Fuse Protection: Each IO channel board is equipped with a miniature fuse, single circuit short circuit does not cause the board to crash
Status Loop Collection: Full open / full close feedback of valves, fans, oil pumps, local interlocks, system auxiliary contacts collection; DO output drives the field electromagnetic valves, sound and light alarms
Simplex Architecture: Single-channel control (no X/Y/Z triple-redundancy), mostly used for non-critical auxiliary machine circuits (lower cost compared to TDBTH6 TMR board)
Application Scenarios
GE heavy-duty gas turbines, steam turbines, combined cycle power plants Mark VIe / VIeS DCS
Power plant auxiliary equipment systems, lubrication stations, cooling water pumps, vent valves, local auxiliary interlock IO points
Non-protection circuits of gas compression units of refinery gas compressors matching VIe control system
Comparison of Identical Models Table
Model Architecture Usage
IS200TDBTH2ACD Simplex single channel Ordinary auxiliary equipment DI/DO (in stock and commonly used)
IS200TDBTH6ACD TMR triple redundancy Unit main protection, trip-related DI/DO
IS200TDBSH2A Compact terminal board with small number of points 8/16-point streamlined IO package