Product number Model: CC-PCNT01
Product Type: Digital input 24 VDC
IOM block name: DI-24
Description: Low Voltage Digital Input (24 volts DC)
Number of channels: 32
Similar to the PMIO type: DI or DI24V
Digital input 24VDC is a missing input/source input type (IEC Class I missing input) module.
The rated voltage of the digital input 24VDC is 24VDC, Logic 1 is 15VDC or 2.5mA (minimum), Logic 0 is 5VDC or 1mA (maximum), the input current is from the load voltage L+(no load) Max 90mA, and from the backplane bus 5VDC Max 130mA.
Digital input 24VDC with photoelectric isolation (field power supply and logic power supply), 500VAC, 1 minute isolation group 4, allowed working temperature 55°C, the cable length is shielded 500m, not shielded 300m and so on.
The C300 controller supports “C Series” products
Use the C Series 24VDC power supply
●8+1 port (FTE switch)
– The safest choice for the L1 layer control environment
– Two Firewalls support the FTE function
– Supports redundancy
– Support power on and running self-diagnosis, with fault indication;
-. Uplink information control, intra-cabinet communication
Highest priority;
– Broadcast information storm suppression
– The controller is not affected by the traffic of the upper-layer IP network.
● Optical fiber interface is optional
– Optical fiber (FO) for. Upper level device connection
– Single mode fiber (15 km)
– Multi-mode fiber (2km)
● Analog input card (support HART protocol) -CC-PAIH01
● Analog input card (HART protocol not supported)- CC-PAIX01
● Analog output card (support HART protocol)- CC-PAOH01
● Analog output card (HART protocol not supported)- CC-PAOX01
● Digital Input card (24VDC)– CC-PDIL01
● Digital input card (support SOE) -CC-PDIS01
● Digital input card (high voltage)– CC-PDIH01
● Digital output card (24VDC) -CC-PDOB01
● Digital output card (with relay board)- CC-PDOB01
● Multi-channel low-level analog input card – CC-PAIM01(mainly used for thermal resistors and thermocouples)
The C300 consists of several parts:
– Controller hardware
– Control Execution Environment (CEE)
– The corresponding mechanical parts? Power supply in the cabinet? Control network interface
– Fault Tolerant Ethernet (FTE) ? 2 Local I/O Link interface
– Run CEE (Control Operating System)